  1. Added by G. N. of 24th May, 1969. 1[3-A. Certificate of Stability:- (1) No manufacturing process shall be carried out in any premises of a factory constructed, reconstructed or extended or in any premises which has been taken into use as a factory or part of a factory until a certificate of stability issued by a competent person in respect of every work of engineering construction in the Form 1-A has been sent by the Occupier of the factory to the Chief Inspector of Factories, and approved by him: 1. Ins. by G. N., dt. 13-3-1994 published in M.G.G., Pt. I-L (Extra), dt. 19-7-84, P. 197. 1[4. Use of premises as a factor:-- No occupier shall use any premises as a factory unless.- (2) Every such application shall be accompanied by a treasury receipt or the cheque or by an Indian Postal Order or an invoice for book adjustment, as the case may be, for payment of the fees prescribed for the purpose as specified by the 2[Schedule below as applicable] 3[with effect from the 1st January 1990]:- Footnotes: 1[Schedule 2[A]

    Quantity of H.P< xml:namespace prefix = o ns = "urn:schemas-microsoft-com:office:office" />

    Installed Maximum

    H. P.

    Nil upto 10

    Upto 9

    Form

    10

    to 20

    Form 21

    to 50

    Form 51

    to 150

    Form 151

    to 250

    Form

    251 to

    500

    Form

    501 to

    1000

    Form

    1001 to

    2500

    Form

    2501 to

    4000

    Form

    4001

    and

    above

    (2)

    Rs.

    100

    200

    (3)

    Rs.

    125

    400

    (4)

    Rs.

    250

    750

    (5)

    Rs.

    1000

    2000

    (6)

    Rs.

    1500

    3000

    (7)

    Rs.

    3000

    4500

    (8)

    Rs.

    6000

    9000

    (9)

    Rs.

    12000

    18000

    (10)

    Rs.

    18000

    24000

    24000

    30000

    Above 10 but not

    above 50

    300

    700

    1250

    3000

    4500

    6000

    12000

    22500

    27500

    33000f

    Above 50 but not

    above 100

    800

    1250

    1750

    4500

    6000

    9000

    15000

    27000

    30000

    36000

    Above 100 but not

    above 500

    1800

    2500

    3500

    9000

    12000

    15000

    22500

    30000

    36000

    42000

    Above 500 but not

    above 1000

    3500

    4000

    7500

    12000

    16500

    19500

    30000

    36000

    42000

    48000

    Above 1000 but

    not above 2000

    5000

    7000

    9500

    16500

    19500

    24000

    33000

    42000

    48000

    54000

    Above 2000

    7000

    9500

    16500

    19500

    24000

    33000

    42000

    48000

    54000

    60000

    2. Subs. by G. N. Of 22-5-1984. 3. Schedule ''A'' Subs. By G. N. dt. 20-10-1998.

    General Capacity in Megawatts

    Number of workers

    Upto 100

    From 101 to 500

    From 501 to 1000

    Over 1000

    Rs.

    Rs.

    Rs.

    Rs.

    Upto 20 M. W.

    1,200

    1,800

    3,000

    4,500

    Over 20 M.W. and upto 50 M.W.

    1,700

    2,700

    4,500

    6,000

    Over 50 M.W. and upto 100

    M.W.

    2,500

    3,500

    6,000

    7,500

    Over 100 M.W. and upto 250

    M.W.

    3,500

    4,500

    7,500

    9,000

    Over 250 M.W. and upto 500

    M.W.

    4,500

    6,000

    9,000

    10,500

    Over 500 M.W. and upto 750

    M.W.

    7,000

    7,000

    10,500

    12,000

    Over 750 M.W. and upto 1000

    M.W.

    7,000

    8,000

    12,000

    15,000

    Over 1000 M.W.

    8,000

    9,000

    15,000

    18,000

    Rated capacity

    More than 9 workers

    Upto 20 M.V.A.

    Over 20 M.VA and upto 50 M.V.A.

    Over 50 M.VA. and upto 100 M.V.A.

    Over 100 M.V.A. and upto 250 M.V.A.

    Over 250 M.V.A. and upto 500 M.VA

    Over 500 M.V.A. and upto 750 M.V.A.

    Over 750 M.VA. and upto 1,000 M.VA

    Over 1,000 M.V.A.

    300

    750

    1,500

    2,200

    3,000

    3,600

    4,500

    6,000

    Footnotes: 1. Subs, by G. N. dt. 20-10-1998.

    Period of Delay

    % of fees

    Upto one month

    5 %

    Upto two month

    10 %

    Upto three month

    15 %

    Upto four months

    20 %

    Upto five months and above

    25 %

    2. Ins. by G. N. dt. 26th July 1991, p. 300. 1[9-A. Revocation of licence:- The Chief Inspector or the Deputy Inspector authorised under sub-rule (1) of rule 8 may, at time before the expiry of the period for which the licence has been granted or renewed, revoke the licence on any pf. the grounds specified in the proviso to sub-rule (1) of rule 6 or in clause (b) of sub-rule (2) of rule 8:

    Coach and motor body works Electric generating or transforming stations.

    Foundries other than foundries in which brass casting is carried on

    Engineering works.

    Gur Factories.

    Factories in which sugar is refined or manufactured.

    Ship-building works.

    1. Ins. and renumbered by G. N. dt. 8-2-1988. 1[22-A. Ventilation and temperature:-- (1) Limits of temperature and air movement.-- In any factory the maximum wet-bulb temperature of air in a work-room at a height of 1.5 metres above the floor level shall not exceed 300°C and adequate air movement of at least 30 meters per minute shall be provided; and in relation to drybulb temperature, the wet-bulb temperature in the workroom at the said height shall not exceed more than that shown in the Schedule hereto, or as regards a dry-bulb reading intermediate between the two dry-bulb readings, that specified in relation to the highter of these two dry bulb readings:

    Dry bulb temperature

    Wet bulb temperature

    30°C to 34°C

    29°C

    35°C to 39°C

    28.5°C

    40°C to 44°C

    28°C

    45°C to 47°C

    27.5°C

    Dry bulb

    Wet bulb

    Dry bulb

    Wet bulb

    Dry bulb

    Wet bulb

    60.0

    58.0

    77.0

    75.0

    94.0

    86.0

    61.0

    59.0

    78.0

    76.0

    95.0

    87.0

    62.0

    60.0

    79.0

    77.0

    96.0

    87.5

    63.0

    61.0

    80.0

    78.0

    97.0

    88.0

    64.0

    62.0

    81.0

    79.0

    98.0

    88.5

    65.0

    63.0

    82.0

    80.0

    99.0

    89.0

    66.0

    64.0

    83.0

    80.5

    100.0

    89.5

    67.0

    65.0

    84.0

    81.0

    101.0

    90.0

    68.0

    66.0

    85.0

    82.0

    102.0

    90.2

    69.0

    67.0

    86.2

    82.5

    103.0

    90.5

    70.0

    68.0

    87.0

    83.0

    104.0

    90.5

    71.0

    69.0

    88.0

    83.5

    105.0

    91.0

    72.0

    70.0

    89.0

    84.0

    106.0

    91.0

    73.0

    71.0

    90.0

    84.5

    107.0

    91.5

    74.0

    72.0

    91.0

    85.0

    108.0

    91.5

    75.0

    73.0

    92.0

    85.5

    109.0

    92.0

    76.0

    74.0

    9,3.0

    86.0

    110.0

    92.0

    Rules 34 to 38 prescribed under sub-section (4) of section 17 1[Rules 34] 2[35. Standards of lighting of factories:- (i) In every factory, where natural lighting is not such that day light conditions are fairly uniform over the working or other areas and/or daylight illumination is not sufficient, additional lighting, which shall be of uniform level, widely distributed to avoid hard shadows or strong contrast and free from direct or reflected glare, shall be provided. The minimum intensity of illumination for the different areas and work-rooms of the type given under column No. 2 shall be as given under column No. 3 of the Schedule 'A' appended hereto;

    Sr. No.

    Area and workroom

    Minimum intensity of

    illumination in Lux

    1.

    Stock-yards, main entrance and exit roads,

    cat-walks of outdoor plants, coal unloading

    and storage areas.

    20

    2.

    Passage-ways, and corridors and stairways,

    warehouses, stock-rooms for large and bulky materials, plat-forms of outdoor plants, basements.

    50

    3.

    Engine and boiler rooms, passengers and

    freight elevators, conveyer creting and boxing departments, store-rooms and stock-rooms rooms, toilet and washrooms.

    100

    Sr. No.

    Name of work

    Example

    Minimum intensity

    Of illumination in

    Lux

    1.

    Where discrimination of detail is not essential,

    Handling of material of coarse nature, rough sorting, grinding of clay products, handling coal

    or ashes.

    50

    2.

    Where slight discrimination of detail is essential.

    Production of semi-finished iron steel products rough assernbling, railing of grains, opening, carding, drawing, siubbing, roving, spinning (ordinary) counts of cottons.

    100

    3.

    Where moderate discrimination of detail is essential,

    Medium assembling, rough bench work and machine work, inspection and testing of products, canning, sawing, venering planning of lumber, sewing of light coloured textiles and leather products, weaving light thread, warping, slashing doubling (fancy) spming

    fine counts.

    200

    4.

    Where close discrimination of detail is essential.

    Medium bench and machine work 300 fine testing, flour grading, leather finishing, weaving cotton goods, or light coloured woolen goods, welding sub-assembly, drilling, rivettng, book-binding and folding.

    300

    5.

    Whre discrimination of fine detail is involved under a fair degree of contract for long periods of time.

    Fine assembling, fine bench and machine work, fine inspection, fine polishing and beveling of glass, fine wood working, weaying dark coloured woolen goods.

    500

    6.

    Where discrimination of extremely fine detail is involved under conditions of extremely poor contrast for long periods of time.

    Extra fine assembling, extra fine inspection, testing of extra fine instruments, jewellery and watch manufacturing, grading and working of tobacco products, dark cloth hand tailoring, final perching in dye works, make-up and proof reading in printing plants.

    1000

    1. Subs. by G. N. dt. 29 May 1976. 1[38. Exemption from rule 35:- Nothing in rule 35 shall apply to the parts of factories specified in the schedule annexed hereto. 48. Urinal accommodation:-- There shall be at least one urinal for every 50 male workers or part thereof employed at a time; provided that where the number of males employed exceeds 500 it shall be sufficient if there is one urinal for every 50 males up to the first 500 and one for every 100 or part thereof thereafter. 1[149. Drainage system for latrines and urinals:- Latrines and urinals shall either be of flush type or aqua-privy type and connected with an underground sewerage system as prescribed under rule 50 or connected to an efficient system of septic tanks: 1. Sub. by G. N. dt. 17th April 1975. 1[50. Certain latrines and urinals to be connected to sewerage system:- Where any general system of underground sewerage with an assured water supply for any locality is provided by a local authority all latrines and urinals of a factory situated in such locality shall be connected with that sewerage system.] 53. Water taps in latrines:- Water taps, conveniently accessible, shall be provided in or near such latrine accommodation. There shall be a least one tap for every ten latrines or part thereof. The water taps shall be connected to the Municipal water supply or to an overhead storage tank of sufficient capacity, so that water is available from the taps during all hours when the workers are in the factory. 1[53A. Number of Sweepers:- In every factory employing number of workers in any shift as shown in column No. 2 of the Schedule...